UK HQ Your time

Biofouling and Legionella Control in Cooling-Water Systems

Legionella pneumophila is the causative agent of Legionnaires’ disease, a severe and potentially fatal pneumonia. Cooling towers and their associated water circuits are the most common environmental source of Legionella outbreaks: the combination of warm water (25–45 °C optimal growth range), nutrients, biofilm niches, and the generation of aerosols from cooling tower drift makes them ideal amplification sites. UK law (Health and Safety at Work etc. Act 1974) requires all operators of cooling towers to assess and control Legionella risk under HSE Approved Code of Practice L8 (2013) and HSG274 Part 1 (2014).

Biofouling — the attachment and growth of microbial biofilm on heat-exchanger surfaces, pipework, and tower packing — is both a Legionella risk factor (biofilm protects Legionella from biocide contact) and an independent operational problem: a 0.1 mm thick biofilm on condenser tubing reduces heat transfer coefficient by 15–20%, equivalent in thermal efficiency impact to a 2–3 °C increase in CIT. Combined biofouling and Legionella management is therefore both a legal requirement and an economic imperative.

HSE L8 mandatory requirements for cooling towers: (1) Written scheme of control documenting risk assessment, control measures, monitoring, and responsible persons. (2) Quarterly monitoring: Legionella (BS EN ISO 11731:2017), heterotrophic plate count (TVC). (3) Temperature management: bulk water < 20°C (or treated above 60°C for recirculating systems). (4) Biocide programme with documented doses, residuals, and product compatibility. (5) Notification to local authority (LA) when cooling tower commences/ceases operation (SI 1992/2225).

Legionella Monitoring Thresholds and Response Actions

Legionella Result (cfu/L)StatusRequired ActionHSG274 Reference
< 100SatisfactoryContinue routine control programme; document resultHSG274 Table 2.2
100–1,000Action levelIncrease monitoring frequency; review biocide programme; inspect system; consider hyperchlorinationHSG274 Table 2.2
1,000–10,000Investigate immediatelyImmediate system review; increase biocide; notify responsible person; consider shutdown for cleaningHSG274 Table 2.2
> 10,000Immediate actionShut down system; hyperchlorinate (HSG274 protocol); notify HSE; do not restart without remediation and clearance testHSG274 Table 2.2; RIDDOR notification if disease occurs

Six-Step Legionella and Biofouling Control Programme

1

Risk Assessment and Written Scheme

Commission a Legionella risk assessment by a competent person (HSE definition: appropriate level of knowledge, training and experience). Document all cooling system components, water volumes, temperature ranges, and biofilm risk areas. Prepare a Written Scheme of Control covering all required monitoring, treatment, and corrective action procedures. Review annually and after any significant system change.

2

Biocide Programme Design

Design dual biocide programme: oxidising biocide (sodium hypochlorite 0.5–1.0 mg/L free Cl₂ as continuous residual; or chlorine dioxide; or bromine) for general control, plus non-oxidising biocide (DBNPA, isothiazolinone) on 2-weekly slug dose for biofilm penetration. Confirm biocides are compatible with corrosion/scale inhibitors and are REACH-registered for this application.

3

Continuous Chlorine Residual Monitoring

Install online chlorine residual analyser at cooling tower basin. Maintain 0.5–1.0 mg/L free chlorine at all times (HSG274 target range). Automated dosing pump triggered by residual probe. Daily manual check with DPD test tablets. Record all residual readings; any deviation below 0.2 mg/L for more than 1 hour triggers immediate investigation.

4

Temperature Management via Destratification

Where the cooling reservoir supplies water to the cooling tower at elevated temperature (due to summer stratification), destratification reduces bulk water temperature by 2–4°C. Lower bulk temperature: reduces Legionella growth rate (halving of growth rate per 5°C reduction below 35°C); allows biocide programme to operate within HSG274 targets more consistently; reduces cooling tower drift temperature.

5

Quarterly Legionella Sampling

Sample at cooling tower basin, make-up water inlet, and at least one remote point on the distribution system. Sample immediately before and 2 hours after biocide dose. Use BS EN ISO 11731 quantitative culture method (14-day incubation). Record results and compare to threshold table. If 100–1,000 cfu/L: increase sampling to monthly until two consecutive < 100 cfu/L results.

6

Annual System Clean and Inspection

At least annually (or when system is shut down): drain, physically clean, and disinfect cooling tower packing, basin, and distribution system. Hot-water flush of dead-legs at > 60°C for 1 hour minimum. Inspect fill media for blockage and biofilm. Replace degraded packing. Re-commission with new biocide programme and Legionella clearance test before returning to service.

Related Pages

Need an aeration solution for your waterbody?

Send us your site parameters and water quality challenges — we will design the right system for your specific waterbody type.

Industries We Serve

Our expertise spans multiple industries with sector-specific water treatment solutions.